CellarMate wine cooling units are designed to operate at or above their rated capacities for total BTUH and CFM under recommended conditions.
Performance
| Model Number: | 025 | 050 | 088 | 200 |
| Nominal Tonnage (Tons): | 1/4 | 1/2 | 1 | 2 |
| Nominal Compressor (hp): | 1/3 | 1/2 | 1 | 2.5 |
Net Cooling Capacity
| Model Number: | 025 | 050 | 088 | 200 |
| @ 70°F Ambient (BTUH): | 3300/3650 | 5600/6050 | 8400/9100 | 16200/17750 |
| @ 80°F Ambient (BTUH): | 3000/3300 | 5300/5700 | 7800/8450 | 15200/16550 |
| @ 90°F Ambient (BTUH): | 2800/3050 | 4850/5275 | 7300/7900 | 14100/15350 |
- Net cooling at cellar temperature and humidity of 55°F and 60% RH / 60°F and 60% RH and at rated airflow.
- Reduce capacity by 3% for each 10% reduction in either condenser or evaporator airflow, 5% for both.
Evaporator Section
| Model Number: | 025 | 050 | 088 | 200 |
| Fan Motor Size (Watts): | 75 | 100 | 195 | 240 |
| Rated Airflow (CFM): | 235 | 430 | 510 | 740 |
| Airflow w/25' Flex Duct (CFM): | 207 | 400 | 485 | 715 |
Condenser Section
| Model Number: | 025 | 050 | 088 | 200 |
| Fan Motor Size (Watts): | 75 | 100 | 195 | 240 |
| Rated Airflow (CFM): | 235 | 430 | 500 | 750 |
| Airflow w/25' Flex Duct (CFM): | 220 | 365 | 475 | 720 |
Typical Testing Data (Factory)
| Model Number: | 025 | 050 | 088 | 200 |
| Head Pressure (psig): | 159 | 140 | 140 | 138 |
| Suction Pressure (psig): | 40 | 30 | 25 | 27 |
| Condenser Inlet Temp. (°F): | 81 | 74 | 97 | 78 |
| Condenser Outlet Temp. (°F): | 98 | 98 | 99 | 107 |
| Evaporator Inlet Temp. (°F): | 56 | 55 | 57 | 55 |
| Evaporator Outlet Temp. (°F): | 44 | 44 | 43 | 46 |
* All ratings at sea level.